The 40 Series base units
can be expanded with up to 6 local expansion modules
for a maximum configuration of 110 digital inputs/outputs
(24 VDC) or 36 analog I/O or a combination of both
digital and analog components. Digital inputs
are electrically isolated 24 VDC (PNP and NPN). Relay
outputs are 250 VAC @ 2A. Transistor outputs are 24
VDC @ 2 x 1A, 4 x 0.5A. Includes a built in RS 232
serial link for programming, ASCII and Modbus.
On-Board
Inputs
On-Board
Outputs
Program
memory
on-line modification
Power
Supply
Type
Order
Code
with
without
8
digital
6
relay
17
kb
34
kb
24
VDC
07
CR 41
ISBP
26 0020 R1001
8
digital
6
relay
17
kb
34
kb
120/230
VAC
07
CR 41
ISBP
26 0021 R1001
8
digital
6
transistor
17
kb
34
kb
24
VDC
07
CT 41
ISBP
26 0022 R1001
8
digital, 3 analog
6
relay
17
kb
34
kb
24
VDC
07
CR 42
ISBP
26 0023 R1001
8
digital, 3 analog
6
relay
17
kb
34
kb
120/230
VAC
07
CR 42
ISBP
26 0024 R1001
8
digital, 3 analog
6
transistor
17
kb
34
kb
24
VDC
07
CT 42
ISBP
26 0025 R1001
50 Series Central Processing
Units
The 50Series base units
can be both expanded with up to 6 local expansion
modules or with up to 32 remote base units, each with
up to 6 local expansion modules. Locally the 50 Series
will support a maximum configuration of 110 digital
inputs/outputs (24 VDC) or 36 analog I/O or a combination
of both digital and analog components. Remotely, it
will support up to an additional 1000 I/O. Digital
inputs are electrically isolated 24 VDC (PNP and NPN).
Relay outputs are 250 VAC @ 2A. Transistor outputs
are 24 VDC @ 2 x 1A, 4 x 0.5A. Includes a built
in RS 232 serial link for programming, ASCII and Modbus.
Has an additional AC31 bus also suitable for Modbus
slave protocol and a real time clock.
On-Board
Inputs
On-Board
Outputs
Program
memory
on-line modification
Power
Supply
Type
Order
Code
with
without
8
digital
6
relay
17
kb
34
kb
24
VDC
07
KR 51
ISBP
26 0010 R1001
8
digital
6
relay
17
kb
34
kb
120/230
VAC
07
KR 51
ISBP
26 0011 R1001
8
digital
6
transistor
17
kb
34
kb
24
VDC
07
KT 51
ISBP
26 0012 R1001
90
Series Central Processing Units
The 90 Series base units
can be expanded through an extensive list of remote
I/O modules up to about 1000 I/O. Digital inputs are
24 VDC. Relay outputs are 250 VAC @ 2A. Transistor
outputs are 24 VDC @ 0.5A. Each processor includes
at least one RS 232 serial link for programming and
an ASCII/AC31 bus along with a real time clock.
On-Board
Inputs
On-Board
Outputs
Program
memory
Power
Supply
Type
Order
Code
20
digital
12
relay
28
kb
120/230
VAC
07
KR 91-R303
GJR
525 0000 R0202
GJR 525 0000 R0303
20
digital
12
relay
28
kb
24
VDC
07
KR 91-R353
GJR
525 0000 R0252
GJR 525 0000 R0353
12
digital
4 analog
8
transistor
2 analog
28
kb / 56 kb
24
VDC (A)
07
KT 92 -R202
GJR
525 0500 R0202
12
digital
4 analog
8 transistor
2 analog
28
kb / 56 kb
24 VDC (B)
07 KT 92 -R262
GJR 525 0500 R0262
24
digital
16
transistor
30
kb / 60 kb
24
VDC (A)
07
KT 93 -R101
GJR
525 1330 R0101
24
digital
16
transistor
32
kb
24
VDC (B)
07
KT 93 -R161
GJR
525 1300 R0161
24
digital
16
transistor
60
kb / 60 kb
24
VDC (B)
07
KT 93 -R171
GJR
525 1300 R0171
24
digital
8 analog
8 config I/O
16
transistor
4 analog
240
kb
24
VDC (A)
07
KT 94 -R101
GJR
525 2100 R0101
24
digital
8 analog
8 config I/O
16
transistor
4 analog
240
kb
24
VDC (B)
07
KT 94 -R161
GJR
525 2100 R0161
(A) Contains
a second RS 232 serial link for ASCII
(B) Contains a second RS 232 serial link for ASCII MODBUS®
and incorporated ARCNET® protocol.
(C) Contains a second RS 232 serial link for ASCII MODBUS®
and incorporated Profibus® protocol.
(D) Contains a second RS 232 serial link for ASCII MODBUS®
and incorporated ARCNET® and Profibus protocols.
12
digital
4 analog
8
transistor
2 analog
240
kb
24
VDC
07
KT 95 -R100
GJR
525 2800 R0100
24
digital
16
transistor
240
kb
24
VDC
07
KT 96 -R100
GJR
525 2900 R0100
24
digital
8 analog
8 config I/O
16
transistor
4 analog
240
kb
24
VDC
07
KT 97 -R100
GJR
525 3000 R0100
24
digital
8 analog
8 config I/O
16
transistor
4 analog
240
kb
24
VDC (B)
07
KT 97 -R160
GJR
525 3000 R0160
24
digital
8 analog
8 config I/O
16
transistor
4 analog
240
kb
24
VDC (C)
07
KT 97 -R120
GJR
525 3000 R0120
24
digital
8 analog
8 config I/O
16
transistor
4 analog
240
kb
24
VDC (D)
07
KT 97 -R162
GJR
525 3000 R0162
(A) Contains
a second RS 232 serial link for ASCII
(B) Contains a second RS 232 serial link for ASCII MODBUS®
and incorporated ARCNET® protocol.
(C) Contains a second RS 232 serial link for ASCII MODBUS®
and incorporated Profibus® protocol.
(D) Contains a second RS 232 serial link for ASCII MODBUS®
and incorporated ARCNET® and Profibus protocols.